Condition monitoring XML for ND9000H rev.2 and rev.3

To add ND9000 rev2 and rev.3 in condition monitoring you need to add new Condition Monitoring description (XML-file) for the new device revision.

Condition monitoring description will be added to the next FieldCare setup (1.5) but with FieldCare 1.3 and 1.4 description file have to be updated manually according to these instructions:

  • Close FieldCare frame application and Condition Monitoring
  • Copy the created descriptions xml under path

FieldCare\CM\XML\CM\[bustype]\[manufacturer]\[devicetype], in our case it means: "C:\Program Files\Metso Automation\FieldCare\CM\xml\cm\HART\Neles Controls\ND9000"
  • Open Windows command prompt and go to CM installation folder (FieldCare\CM), e.g. "C:\Program Files\Metso Automation\FieldCare\CM"
  • Run the following command from command line:
fmpdb /installdtds

A progress bar is shown during update.

The update routine compares the dates of files on disk and the dates in database. If the date differs, then the description is imported.
Note that the exact location of description does not matter as long as the description can be found under FieldCare\CM\xml\CM folder.